Fault messages of RLS 45 K

LEDs flash, Fault LED = On

 

Internal error in RLS room air control

Fault rectification: Ensure that no voltage is present, restart the control. To perform a reset of the control, press

Press + for 5 seconds.

 

Overtemperature/overload of mains adapter

Fault rectification: Check the ambient temperature and allow the mains adapter to cool down.

 

No communication or failure of the external power units/RLS or ventilation units (PPB 30 K, RV 2, CPP 60)

Fault rectification: Check the connection to the LT power unit/RLS room air controls and PPB 30 K, RV 2 or CPP 60 ventilation units. Check the settings in the software (e.g. activated LTs and ventilation units that are not connected). Incorrect addressing (e.g. two slaves with the same address).

 

No communication and/or failure of the sensors (RS 485, I2C)

Fault rectification: Check connection to the sensors. Check settings in the software (activated sensors that are not connected).

 

Internal system error – RLS slave power unit / ventilation unit

Fault rectification: Switch off the voltage.

 

No communication with the EnOcean module (PP 45 EO)

Fault rectification: Check wiring. If the connection is correct, the error disappears.

 

No communication with taught-in sensor

Fault rectification: Check cable connection to taught-in sensor.