Automatic search (Plug & Play)
In the automatic search, the factory-set unit addresses (100 to 250) of the individual ventilation units are read out. The supply air and exhaust air units of the same unit family (RV 2 or CPP 60) are then paired.
Alternatively, you can also carry out the process manually using the commissioning software. This is required for an uneven number of units. For manual configuration → RV 2 installation and commissioning instructions.
For RV 2 unit address, see sticker next to the connection terminal.
Make sure that an even number of units from the same unit family are installed and that no unit address is used more than once (otherwise a communication error will occur and the search will not be saved). Otherwise, reconfigure the factory address of the individual units using the commissioning software.
Start automatic search
- Call up the service menu.
- Select the last parameter Plug & Play. The 3 LEDs on the left flash slowly.
- Use
to select 1 = Start Plug & Play search. During the search run, the ventilation level LEDs light up (running light, approx. 1 minute). Cancel with
. The supply air and exhaust air units are automatically paired with the determined unit addresses.
The values are saved after a successful search. The number of units found is displayed with the ventilation level LEDs.
The units are categorised in chronological order, alternating between supply air and exhaust air units.
Example with 4 ventilation units and addresses 110 / 180 / 185 / 220. Automatic categorisation as follows: 110 = supply air / 180 = exhaust air / 185 = supply air / 220 = exhaust air.
0 | 1 | 2 | 3 | 4 | 5 |
|
|
|
|
|
|
Connected RV 2 ventilation units
0 | No ventilation unit |
1 | 1 ventilation unit |
2 | 1 pair of units |
3 | 2 pairs of units |
4 | 3 pairs of units |
5 | 4 pairs of units |
| Error when connecting an odd number of units |
If the search fails, the ventilation level LEDs indicate a fault
and flash quickly.
To delete the settings, select 1 = Start plug & play search with
.
For RV 2 and CPP 60 units when assigned in pairs (even number of units).