Intermittent ventilation/intensive ventilation with ventilation level 5
All connected ventilation units are switched on for 30 minutes with an optional button on the 230 V switching contact.
The intermittent ventilation parameter must be set in the Service menu. The switch-on duration can be adjusted with the commissioning software, 230 VAC input, Duration of ventilation level 5 parameter (setting range 5...90 minutes).
If any button on the control is pressed during intermittent ventilation, the ventilation units switch back to the ventilation level used previously.