Supply air mode for exhaust air fans with run-on time
Run-on time 0, 6 or 15 minutes
The RLS 45 K controls the CPP 60 ventilation units and exhaust air fans connected to the 230 V input (ECA 100 ipro, ER 60).
If the switch-on of an exhaust air fan is detected, all PushPull ventilation units connected to the respective RLS 45 K (CPP 60, RV 2, PP 45 and PPB 30) switch to supply air mode. A volumetric flow compensation takes place to compensate for the resulting negative pressure.
The volumetric flow compensation is set to a total of 60 m³/h for exhaust air units.
Only use exhaust air units with an exhaust air volumetric flow of 60 m³/h, e.g. ER or ECA 100 pro. When an exhaust air fan starts up, the PushPull units go into supply air mode to compensate for the negative pressure produced.
Once the set run-on time has elapsed, the ventilation units switch back to the previously selected ventilation level.
Sensor-controlled exhaust air units with automatic start-up are not recognised by the RLS 45 K.
For correct operation, the correct number of units must be stored in the service menu.