Setting up additional function
The additional components are connected to the separate 230 V input of the RLS 45 K
DANGER of electric shock if incorrectly connected to the 230 V input of the control unit.
Ensure a phase balance between all components connected to the ventilation system.
- Switch off the mains fuse and secure it against being switched on again.
- Electrically wire additional components (buttons, switches, timers, exhaust air fans, etc.) to the 230 V input of the RLS 45 K with the additional components, see connection and wiring diagrams in the appendix.
- Insert RLS 45 K into the flush-mounted box and screw down to flush-mounted box with 4 screws.
- Attach the outer frame. Make sure it locks into position. With the HYI sensor installed, ensure that the sensor opening (hole) is positioned above the sensor.
- Switch on ventilation system with the mains fuse.
- Activate the 230 VAC input in the service menu of the RLS 45 K.
- Use the commissioning software to select the setting parameter RLS 45 K function 230 VAC input and the desired additional function under Installer level/Basic settings. The 230 V function can also be selected in the service menu.
- To set a supply air run-on time, select the Supply air function run-on time parameter and set the run-on time to 0, 6 or 15 minutes. Available setting values depend on the connected unit, e.g. ER 60 VZ 15 has a run-on time of 15 min.
- Carry out a function test with the set values.