Installing DS 45 RC (EnOcean) radio switch
Radio-controlled operation of the CPP 60 ventilation units is possible with the DS 45 RC radio switch and an EnOcean module PP 45 EO (RS 485). Observe the permissible ranges → chapter Technical data.
- Installation location: Do not mount the receiver, with internal antenna, on the wall side of the transmitter.
- Only the EnOcean module PP 45 EO is taught-in on the master ventilation unit. Radio switches are taught-in directly to the PP 45 EO.
- The radio switch can be activated in the service menu of the RLS 45 K control or with the CDV commissioning software.
- Switch off the mains fuse and secure it against being switched on again.
- Glue the DS 45 RC to the wall at the installation location. Alternatively, the radio switch can also be screwed onto the wall (mounting material provided by customer).
- Connect the EnOcean extension module PP 45 EO to the RLS 45 K control (terminals RS 485 bus) → Connection and wiring diagrams in the appendix and accessory instructions. If necessary, install a separate distributor for the wiring.
- Connect the RLS 45 K room air control to the PC/notebook.
- Switch the mains fuse on.
- Call up the service menu of the RLS 45 K or CDV commissioning software.
- Activate EnOcean.
- Call up EnOcean Teach mode and send a Teach telegram. The radio switch is automatically taught-in to the PP 45 EO.
Installation instructions