Operation with frequency converter

Speed control is only permitted with a suitable frequency converter of type MFU ... which is to be provided by the customer (Frequency converter operating instructions).

In this case, the motor is protected by the frequency converter. The output frequency of the converter must not exceed 50 Hz. Speed control with a transformer is not permitted. When operating with a frequency converter, avoid excessively long motor supply cables.