Manual humidity control
The control regulates the unit according to the configured switch-on points 1 & switch-on point 2 as well as the selected airflow switch-on point 1 and the max. airflow humidity.
Once the unit is installed, it adjusts to the room humidity prevailing at that time (relative humidity). This rel. humidity is permanently measured and compared with the selectable switch-on point 1. If the relative humidity exceeds switch-on point 1, the unit is set to the selected "Airflow switch-on point 1".
Once switch-on point 1 has been exceeded, the relative humidity continues to be measured and compared with the selectable switch-on point 2. If the relative humidity exceeds switch-on point 2, the unit is set to the selected "max. airflow humidity".
If switch-on point 2 is undershot, the unit is set to "Airflow switch-on point 1".
If switch-on point 1 is not reached, the unit is set to the initially operated level.
Dehumidification mode selected manually.