Safety instructions for electrics
DANGER Danger if the relevant regulations for electrical installations are not observed.
- Before removing the housing cover or removing the fan insert and before installing the electrics, switch off all supply circuits, switch of mains fuse and secure it against being accidentally switched back on again. Attach a warning sign in a clearly visible place.
- Be sure to observe the relevant regulations for electrical installation; e.g. DIN EN 50110-1. In Germany, particularly observe VDE 0100, with the corresponding sections.
- A mains isolation device with contact openings of at least 3 mm at each pole is mandatory.
- Only connect unit to permanently wired electrical installation and with NYM-O or NYM-J cables, depending on the unit variant, 3 x 1.5 mm² or 5 x 1.5 mm².
- Units may only be operated using the voltage and frequency shown on the rating plate.
- Unit may be energized even when at a standstill and may switch on automatically due to sensors (time delay, humidity etc.). Maintenance and fault finding only permissible when carried out by qualified electricians.
- The degree of protection stated on the rating plate is only guaranteed if installation is undertaken correctly and if the connecting cable is correctly guided through the stepped grommet (The grommet must completely enclose the cable sheathing). The fan insert must also be engaged and the housing cover installed.
- Ensure sufficient supply air during operation.
DANGER Danger due to fire transmission
- if an incorrect connection duct is connected to the housing. Always use the correct cable material for the respective housing. Requirements in line with approval.
- if an incorrect ceiling compound is used for exhaust air systems with an intermediate ceiling (ceiling barrier system). Ensure that the gap remaining between the main duct and wall or ceiling is fully sealed with non-flammable materials resistant to deformation, such as concrete, cement mortar or plaster.