ER-UPD EC single-room installation

5

Metal discharge connection with shut-off damper

18

Main duct, steel folded spiral-seams duct

19

Connection duct, steel folded spiral-seams duct DN 75/80

20

Power cable

37

UPM 60/100 mounting support

38

Plaster protective cover

39

Cable grommet

40

ER-MO expanded rubber

X4

Clamping band or steel threaded rod with duct clamp

  1. Remove the plaster protective cover from the housing.
  2. NOTICE The unit will be damaged and function impaired if the fixing screws used are incorrect/too long.

    Fixing screws may not penetrate into the housing.

    1. Use the screws provided (UPM 60/100 mounting support).
  3. For suspended ceilings, cut mounting support to the required length, bend it into shape and attach it to the ER-UPD EC housing using the enclosed screws.
  4. Mark fixing holes for mounting support on ceiling, drill dowel holes and insert steel dowels.
  5. DANGER Danger of short-circuits and damage to the unit.

    If the cable grommet is not installed correctly, water may penetrate the housing. The degree of protection can no longer be guaranteed.

    1. Drive through cable grommet so that it can seal the cable sheathing all the way round (circular, no slots).
  6. Guide power cable from rear of housing through cable grommet into housing.
  7. Move housing into desired position and secure to ceiling with both mounting supports.
  8. DANGER Fire may spread if connection duct is incorrectly installed.

    1. Only use permitted duct material (Requirements in line with approval).
    2. Correctly attach connection duct to exhaust socket.
  9. Slide connection duct to stop above discharge connection. Secure connection duct and discharge connection with 3 steel blind rivets. Then seal well for ventilation, e.g. with cold-shrink tape.
  10. Make electrical connection.
  11. Insert the plaster protective cover in the housing.
  12. Plaster in housing flush with front edge, note tile thickness if necessary: Important information about plastering.