Covers: Functions

 

ER-A

ER-AK NFC

ER-AH NFC

ER-AB NFC

Parameterisable via Maico@NFC APP

 

Filter change indicator
(6 months) with TimeStrip

 

 

 

Filter change indicator
(6 months) with LED

 

Control with time module

 

Control with fully automatic humidity control: Air extraction takes place automatically if the switch-on humidity is exceeded.

 

 

 

Control with manual humidity control: Air extraction takes place when humidity switch-on points 1 and 2 are exceeded.

 

 

 

Control with motion detector. Full load level after motion is detected (range motion sensor is 5 m)

 

 

 

Barrier-free product, as it switches itself on and off automatically

 

 

Not speed-controllable

Electrical plug-in connection for quick connection of the ER EC with ER GH housing and ER-AK NFC, ER-AH NFC or ER-AB NFC with the ER EC/ER EC 2.1fan insert.

 

Airflow volume of base load 30 m³/h for continuous operation

●*

●*

●*

●*

Airflow volume of the base load and full load levels can be set

 

Additional airflow volumes that can be set
in base load: 15-100 m³/h and full load 15-100 m³/h

 

●***

Full load level on/off via light switch or separate switch. During manual operation (e.g. using light switch), the start delay and run-on time apply.

Full load operation (60 m³/h) with start delay of 60 seconds and run-on time of 15 minutes, non-adjustable

●*

 

 

 

Full load operation (60 m³/h), start delay can be set with 0–120 seconds in 5-second increments

 

●**

Run-on time of the full load level adjustable 0–30 minutes in 1-minute increments

 

Adjustable interval control for ventilating rooms that are not regularly used. Time interval adjustable 0–24 hours in 1 hour increments, operating time adjustable at intervals.

 

Operating time adjustable at intervals of 10–60 minutes in 10-minute increments

 

Interval control can be switched off.

 

Switching option: The base load can be switched on or off by an additional switch (Electrically connecting the unit).

* Factory setting: Tolerance of time details max. ± 5 %

** For the ER-AB NFC, the start delay only affects the light switch operation.

*** For ER-AH NFC humidity control, 15–40 m³/h can be set for base load and 40–100 m³/h for full load.