Covers: Functions
| ER-A | ER-AK NFC | ER-AH NFC | ER-AB NFC |
|---|---|---|---|---|
Parameterisable via Maico@NFC APP |
| ● | ● | ● |
Filter change indicator | ● |
|
|
|
Filter change indicator |
| ● | ● | ● |
Control with time module |
| ● | ● | ● |
Control with fully automatic humidity control: Air extraction takes place automatically if the switch-on humidity is exceeded. |
|
| ● |
|
Control with manual humidity control: Air extraction takes place when humidity switch-on points 1 and 2 are exceeded. |
|
| ● |
|
Control with motion detector. Full load level after motion is detected (range motion sensor is 5 m) |
|
|
| ● |
Barrier-free product, as it switches itself on and off automatically |
|
| ● | ● |
Not speed-controllable | ● | ● | ● | ● |
Electrical plug-in connection for quick connection of the ER EC with ER GH housing and ER-AK NFC, ER-AH NFC or ER-AB NFC with the ER EC/ER EC 2.1fan insert. |
| ● | ● | ● |
Airflow volume of base load 30 m³/h for continuous operation | ●* | ●* | ●* | ●* |
Airflow volume of the base load and full load levels can be set |
| ● | ● | ● |
Additional airflow volumes that can be set |
| ● | ●*** | ● |
Full load level on/off via light switch or separate switch. During manual operation (e.g. using light switch), the start delay and run-on time apply. | ● | ● | ● | ● |
Full load operation (60 m³/h) with start delay of 60 seconds and run-on time of 15 minutes, non-adjustable | ●* |
|
|
|
Full load operation (60 m³/h), start delay can be set with 0–120 seconds in 5-second increments |
| ● | ● | ●** |
Run-on time of the full load level adjustable 0–30 minutes in 1-minute increments |
| ● | ● | ● |
Adjustable interval control for ventilating rooms that are not regularly used. Time interval adjustable 0–24 hours in 1 hour increments, operating time adjustable at intervals. |
| ● | ● | ● |
Operating time adjustable at intervals of 10–60 minutes in 10-minute increments |
| ● | ● | ● |
Interval control can be switched off. |
| ● | ● | ● |
Switching option: The base load can be switched on or off by an additional switch (Electrically connecting the unit). | ● | ● | ● | ● |
* Factory setting: Tolerance of time details max. ± 5 %
** For the ER-AB NFC, the start delay only affects the light switch operation.
*** For ER-AH NFC humidity control, 15–40 m³/h can be set for base load and 40–100 m³/h for full load.