Installation
Leakage with unauthorised ventilation ducts.
- Only use approved MAICO flexible ducts, type MF-F.
Leakage from distorted ventilation ducts.
- Ensure distortion-free installation
- Insert the ventilation ducts vertically into the air distributor as far as they will go. When plugging in, listen for a triple click (3x click).
- Ensure a level surface at the installation site.
Risk of injury due to inadequate fastening!- Provide mounting material of sufficient size.
- Screw the air distributor to the wall, ceiling or a bracket using suitable mounting material. Fasten the air distributor in a suspended ceiling with 3 or 4 fastening elements (e.g. threaded rods Fig. A).
- Insert the flexible ducts [6] of the duct branch vertically into the connection openings [3] of the air distributor as far as they will go.
- Insert the flexible duct(s) into the mounting clamp(s) and fasten.
- Close unused air distributor openings with sealing plugs [5].
- Push the DN 160 folded spiral-seams duct directly over the housing connection [2] and seal it additionally. Use the optional plug connector [7] for DN 125 folded spiral-seams duct Fig. F.
In the case of a bent flexible duct, attach a mounting clamp near the distributor. Bend the flexible duct only after the mounting clamp.