Teaching-in PP 45 ACT EnOcean wireless actuator

With the PP 45 ACT EnOcean actuator, radio-controlled PP 45 RC PushPull units can be combined with wired exhaust air units (ECA, ER).

The EnOcean actuator can be used as a normal light switch. The wired exhaust air units (ECA, ER) are switched on at the push of a button.

At the same time, a radio telegram is sent to the PP 45 RC master unit. The PP 45 RC units (master + slave) provide the required supply air at the exhaust air units.

Teaching-in on the PP 45 RC unit (master unit only) is the same as teaching-in a sensor.

Through the master-slave network, both PP 45 RC units provide 30 m³/h of supply air during the “Supply air for exhaust air units” function.

We therefore recommend using the PP 45 ACT only with two PP 45 RC radio-controlled units. The actuator must only be taught-in at the master unit.

Teaching-in PP 45 ACT on the PP 45 RC master unit

  1. Electrically connect PP 45 ACT → Installation instructions for final installation kit, connection diagrams in the appendix.
  2. Check the functions on the exhaust air fan. If these function correctly, switch off the exhaust air unit with the PP 45 ACT.
  3. Set PP45 RC master unit to teaching mode.
  4. Press the T4 button once on the PP 45 ACT. The exhaust air unit switches on. The units are now taught-in to each other.

For installation and commissioning, refer to the enclosed PP 45 ACT installation and operating instructions.

  1. Check the functions on the exhaust air fan. If these function correctly, switch off the exhaust air unit with the PP 45 ACT