Radio components which can be taught-in (EEP protocol)

Radio components must support the EEP protocol. The following radio components with the specified EEP no. are approved for PP 45 / PPB 30 systems.

Type

EEP

DS 45 RC radio switch, 4-channel wall-mounted transmitter

F6-02-01

Humidity/temperature sensor*

A5-04-01

CO2/temperature sensor

A5-09-08

VOC/temperature sensor**

A5-09-05

PP 45 ACT: 1-channel recessed-mounted switch

D2-01-01

* Not available for PPB 30 units.
** No EnOcean VOC sensor currently available.

If within range, up to 8 radio sensors can be used with radio-controlled systems.

DS 45 RC radio switch

The DS 45 RC is a double rocker radio switch for operating PP 45 RC / PPB 30 RC ventilation units. The operating mode and ventilation level is transferred to all taught-in PP 45 RC/PPB 30 RC master ventilation units.

PP 45 EO EnOcean extension module

The PP 45 EO EnOcean extension module allows radio-controlled PP 45 ventilation units to also be operated with the wired RLS 45 K control. The PP 45 EO is connected to the RS 485 interface of the RLS 45 K.

The PP 45 EO EnOcean module can only be taught-in with the commissioning software (RLS 45 K). This activates the teaching mode and sends a radio telegram. All radio sensors/radio switches are taught-in directly on the PP 45 EO. Only the EnOcean module is taught-in on the master unit.

→ Commissioning or Commissioning software.

Radio actuator PP 45 ACT (1 channel)

With the PP 45 ACT, the function "Supply air for exhaust air units" can be activated for PP 45 RC ventilation units. The PP 45 ACT is connected and taught-in in accordance with the enclosed installation and operating instructions.