Electrical specifications of the RLT Flat air handling units and heat registers
Model | Performance details | RCD details | |||
|---|---|---|---|---|---|
Standard unit | PH | EH | Rec. type | Recorded current | |
[kW] | [kW] | [kW] | [mA] | ||
M4004H | 0.27 | 1.5 | 1.5 | B or B+ | 30 |
M4007H | 0.44 | 2.25 | 2.25 | B or B+ | 30 |
M4012H | 0.87 | 4.25 | 4.25 | B or B+ | 30 |
M4020H | 1.1 | 6.75 | 6.75 | B or B+ | 300 |
M4027H | 1.6 | 9 | 9 | B or B+ | 300 |
Recommended fuses for mains connection: D-type "slow"; D-10,000 A – AC3 | |||||
Model | Cable cross-sections | ||||||||
|---|---|---|---|---|---|---|---|---|---|
Standard unit | Unit+PH & Unit+EH | Unit+PH+EH | |||||||
Maximum current | Rec. cable | Rec. fuse | Maximum current | Rec. cable | Rec. fuse | Maximum current | Rec. cable | Rec. fuse | |
[A] | [mm2] | [A] | [A] | [mm2] | [A] | [A] | [mm2] | [A] | |
M4004H | 2.0 | 5x2.5 | 10 | 4.43 | 5x2.5 | 10 | 6.83 | 5x2.5 | 10 |
M4007H | 3.1 | 5x2.5 | 10 | 6.73 | 5x2.5 | 10 | 10.33 | 5x2.5 | 16 |
M4012H | 5.4 | 5x2.5 | 10 | 12.23 | 5x2.5 | 16 | 19.02 | 5x4 | 20 |
M4020H | 5.0 | 5x2.5 | 10 | 15.83 | 5x2.5 | 20 | 26.62 | 5x4 | 32 |
M4027H | 7.0 | 5x2.5 | 10 | 21.42 | 5x4 | 32 | 35.82 | 5x6 | 40 |
The cable cross-section calculations are based on a maximum cable length of 50 m and a voltage drop of 10 % of the supply voltage. For other installations, please contact Maico! | |||||||||
Earthing of the RLT air handling unit is absolutely essential!
The motor is "intrinsically safe" against overload. It is therefore not necessary to install electrical overload protection.
Single-phase – three-phase changeover (only for RLT Flat WITHOUT electric heating register (PH/EH)
All units are manufactured at the factory with three-phase connections. If single-phase operation is required, please proceed according to the specified instructions.
Single-phase operation only applies to the RLT Flat WITHOUT electric heating register!
All changes for the three-phase/single-phase conversion must be made on the power supply side of the circuit-breaker.
The unit must not be switched on and off more often than at intervals of at least 5 minutes.