Installation site, impermissible operation
ATTENTION Damage to the unit if the mounting sleeve is overloaded. Always install the mounting sleeve load-free and do not apply any loads to the mounting sleeve. Do not deform the mounting sleeve. This can otherwise leak and the slide-in module cannot be inserted.
Installation positions not permitted for the pre-installation kit:
- below statically load-bearing components
- in areas with static loads
- in areas that are required for fastening a building element (window/door)
- below statically loaded areas in the safety zone (blue labelling)
Operation is permitted:
- with installation on an exterior wall with sufficient load-bearing capacity and exterior wall thermal insulation 95 mm to 355 mm minus plaster thickness.
- in supply air rooms.
- with free working space 0.7 m in front of the unit (filter change).
- with permanent electrical installation with approved cables and connections.
- exactly levelled with the spirit level and aligned on the exterior wall with vertical installation position.
- with RLS 45 K comfort control for operating a maximum of 8 RV 2 units.
- with at least 1 pair of units, operation in pairs is recommended. A single RV 2 unit can also be combined with an exhaust air fan in the bathroom/WC. Exhaust air fans with up to 60 m³/h (ER 60 or ECA 100 ipro) are permitted.
- with correctly installed external grille with drip edge.
The RV 2 VS pre-installation kit is symmetrically constructed and can be used to the right or left of the soffit.