Screwing the installation unit together
Condensate is discharged into the external cover via a condensate drain integrated in the mounting sleeve where it is drained off via a drip edge. Ensure that the condensate drain is not soiled during and after installation and that it is guaranteed at all times.
- Ensure a clean installation site, remove dirt and dust:
- Only attach the installation unit to walls with sufficient load-bearing capacity.
- The installation unit must be firmly seated and must not wobble.
- Do not install the soffit element / installation unit in combination with 100 mm thick façade insulation.
- Mounting material must be supplied on site.
Danger to health from mould formation due to building and moisture damage caused by incorrect installation or non-compliance with building regulations.
Do not overload or deform the installation unit! Otherwise the housing may leak. The slide-in module can no longer be inserted. Attach the installation unit exactly horizontally.
- Align the installation unit exactly horizontally using a spirit level and insert the internal plaster frame flush with the window soffit.
- Screw the installation unit firmly to the exterior wall.