Fault messages of RLS 45 K

LEDs flash, Fault LED = On

 

Internal error in RLS room air control

Fault rectification: Ensure that no voltage is present, restart the control. To perform a reset of the control, press

Press + for 5 seconds.

 

Overtemperature/overload of mains adapter

Fault rectification: Check the ambient temperature and allow the mains adapter to cool down.

 

No communication or failure of the external power units/RLS or ventilation units

Fault rectification: Check connection to the LT/RLS. Check the settings in the software (e.g. activated LTs that are not connected). Incorrect addressing (e.g. two slaves with the same address).

 

No communication and/or failure of the sensors (RS 485, I2C)

Fault rectification: Check connection to the sensors. Check settings in the software (activated sensors that are not connected).

 

Internal system error – RLS slave power unit / ventilation unit

Fault rectification: Switch off the voltage.

 

No communication with the EnOcean module (PP 45 EO)

Fault rectification: Check wiring. If the connection is correct, the error disappears.

 

No communication with taught-in sensor

Fault rectification: Check cable connection to taught-in sensor.