Max. 3 accessory components per master RLS. Teaching-in on the master RLS.
Wiring to plug-in connection terminal.
Connection cables: 230V: Type NYM-J 5G 1.5 mm² 12 V (RS 485): RLS control to star point/distributor max. 4 m, type J-Y(ST)Y 2x2x0.8 mm². Ventilation unit to star point/distributor max. 25 m, type LiYY 4x0.5 mm².
Parameter settings in the service menu of the RLS 45 O/K control. With RLS 45 K, alternatively also with the commissioning software.
Provide suitable mounting material (screws, dowels) on site.
Use a deep flush-mounted box (depth 66 or 61mm) or double flush-mounted box for accessory components.
Recommendation forPP 45 LT: If there are more than 2 ventilation units, install the PP 45 LT in an electronic switch box (simpler electrical connection).