Manual operating mode

The ventilation unit runs at one ventilation level, until another level or operating mode is selected – with intermittent ventilation, time-limited increase to intensive ventilation.

When operating with an RLS 1 WR or EnOcean wireless components, the operating modes described apply.

In manual operation the measurements of all internal and external humidity sensors are taken into account. Connected external air quality sensors (CO2 and VOC) are not taken into account.

Up to firmware version 1.2.7, the unit excess humidity protection is permanently activated in Manual mode; as of firmware version 1.3.0, there is no permanent activation.

All measurements from internal and external humidity sensors are used for analysis. If the maximum humidity value limit is exceeded, a switch is made to intensive ventilation until the humidity is 3 % below the value limit. The ventilation level is only increased to intensive ventilation if the outside air conditions are actually suited to dehumidification.