WS 160 Flat

Central, flat ventilation unit with heat recovery in five variants with enthalpy heat exchanger, up to 160 m³/h

WS 160 Flat IM0016640.PNG Central, flat ventilation unit with heat recovery in five variants with enthalpy heat exchanger, up to 160 m³/h

Below you can see a direct comparison of the products you have selected. Differences between the products are highlighted in blue.

Article

WS 160 Flat ET

Centralised, highly-efficient ventilation units with EC fans and constant volumetric flow regulation, including enthalpy cross-counterflow exchanger, 2 supply air connections (left and right) and 1 exhaust air connection (centre), air volume 40 - 160 m³/h, connection diameter 4 x DN 125, 4 SVR 125 plug connectors or 90° B90-125 elbow needed to connect folded spiral-seams ducts (order as accessories), the DN160 folded spiral-seam duct can also be placed directly on the EPP connection, including RLS 1 WR control unit, including integrated web server and MAICO app (air@home) for mobile unit control, live reports via web tool, DIBT approval and passive house certificate, KNX and EnOcean connection possible

  • On the notes

WS 160 Flat BET

Centralised, highly-efficient ventilation units with EC fans and constant volumetric flow regulation, including bypass and enthalpy cross-counterflow exchanger, 2 supply air connections (left and right) and 1 exhaust air connection (centre), air volume 40 - 160 m³/h, connection diameter 4 x DN 125, 4 SVR 125 plug connectors or 90° B90-125 elbow needed to connect folded spiral-seams ducts (order as accessories), the DN160 folded spiral-seam duct can also be placed directly on the EPP connection, including RLS 1 WR control unit, including integrated web server and MAICO app (air@home) for mobile unit control, live reports via web tool, DIBT approval and passive house certificate, KNX and EnOcean connection possible

  • On the notes

WS 160 Flat KET

Centralised, highly-efficient ventilation units with EC fans and constant volumetric flow regulation, including preheating register and enthalpy cross-counterflow exchanger, 2 supply air connections (left and right) and 1 exhaust air connection (centre), air volume 40 - 160 m³/h, connection diameter 4 x DN 125, 4 SVR 125 plug connectors or 90° B90-125 elbow needed to connect folded spiral-seams ducts (order as accessories), the DN160 folded spiral-seam duct can also be placed directly on the EPP connection, including RLS 1 WR control unit, including integrated web server and MAICO app (air@home) for mobile unit control, live reports via web tool, DIBT approval and passive house certificate, KNX and EnOcean connection possible

  • On the notes

WS 160 Flat KBET

Centralised, highly-efficient ventilation units with EC fans and constant volumetric flow regulation, including preheating register, bypass and enthalpy cross-counterflow exchanger, 2 supply air connections (left and right) and 1 exhaust air connection (centre), air volume 40 - 160 m³/h, connection diameter 4 x DN 125, 4 SVR 125 plug connectors or 90° B90-125 elbow needed to connect folded spiral-seams ducts (order as accessories), the DN160 folded spiral-seam duct can also be placed directly on the EPP connection, including RLS 1 WR control unit, including integrated web server and MAICO app (air@home) for mobile unit control, live reports via web tool, DIBT approval and passive house certificate, KNX and EnOcean connection possible

  • On the notes

WS 160 Flat KBZET

Centralised, highly-efficient ventilation units with EC fans and constant volumetric flow regulation, including preheating register, bypass, zone shutter and enthalpy cross-counterflow exchanger, 2 supply air connections (left and right) and 1 exhaust air connection (centre), air volume 40 - 160 m³/h, connection diameter 4 x DN 125, 4 SVR 125 plug connectors or 90° B90-125 elbow needed to connect folded spiral-seams ducts (order as accessories), the DN160 folded spiral-seam duct can also be placed directly on the EPP connection, including RLS 1 WR control unit, including integrated web server and MAICO app (air@home) for mobile unit control, live reports via web tool, DIBT approval and passive house certificate, KNX and EnOcean connection possible

  • On the notes
ArticleWS 160 Flat ETWS 160 Flat BETWS 160 Flat KETWS 160 Flat KBETWS 160 Flat KBZET
Product detailsProduct detailsProduct detailsProduct detailsProduct details
  • On the notes
  • On the notes
  • On the notes
  • On the notes
  • On the notes
Product type Centralised ventilation unit Centralised ventilation unit Centralised ventilation unit Centralised ventilation unit Centralised ventilation unit
Article number: 0095.0090 0095.0092 0095.0091 0095.0093 0095.0094
Model

Standard model

Bypass model

Comfort model

Comfort bypass model

Comfort bypass zones model

Number of ventilation levels

4

4

4

4

4

Air flow volume

40 m³/h - 160 m³/h

40 m³/h - 160 m³/h

40 m³/h - 160 m³/h

40 m³/h - 160 m³/h

40 m³/h - 160 m³/h

Volumetric flow constant

yes

yes

yes

yes

yes

SEC average

-34,1 kWh/(m²*a)

-34,1 kWh/(m²*a)

-34,1 kWh/(m²*a)

-34,1 kWh/(m²*a)

-34,1 kWh/(m²*a)

Energy efficiency class

A

A

A

A

A

Type of voltage

Alternating current

Alternating current

Alternating current

Alternating current

Alternating current

Rated voltage

230 V

230 V

230 V

230 V

230 V

Frequency

50 Hz/60 Hz

50 Hz/60 Hz

50 Hz/60 Hz

50 Hz/60 Hz

50 Hz/60 Hz

SPI value in accordance with DIN EN 13141-7 (A7)

0,34 Wh/m³

0,34 Wh/m³

0,34 Wh/m³

0,34 Wh/m³

0,34 Wh/m³

Power consumption in accordance with DIN EN 13141-7 (A7)

36 W

36 W

36 W

36 W

36 W

Stand-by power consumption

< 1 W

not specified

not specified

not specified

not specified

Imax

1,1 A

1,1 A

4,6 A

4,6 A

4,6 A

Degree of protection

IP 00

IP 00

IP 00

IP 00

IP 00

DIBT approval

yes

yes

yes

yes

yes

PHI certification

yes

yes

yes

yes

yes

Installation site

Bathroom / Kitchen / Cellar / Storage tank / Jamb wall / Utility room / Heating room / Hall

Bathroom / Kitchen / Cellar / Storage tank / Jamb wall / Utility room / Heating room / Hall

Bathroom / Kitchen / Cellar / Storage tank / Jamb wall / Utility room / Heating room / Hall

Bathroom / Kitchen / Cellar / Storage tank / Jamb wall / Utility room / Heating room / Hall

Bathroom / Kitchen / Cellar / Storage tank / Jamb wall / Utility room / Heating room / Hall

System type

Centralised

Centralised

Centralised

Centralised

Centralised

Housing material

Plastic EPP/sheet steel

Plastic EPP/sheet steel

Plastic EPP/sheet steel

Plastic EPP/sheet steel

Plastic EPP/sheet steel

Heat exchanger material

Synthetic material

Synthetic material

Synthetic material

Synthetic material

Synthetic material

Inner coating material

Plastic EPP

Plastic EPP

Plastic EPP

Plastic EPP

Plastic EPP

Colour

black / traffic white

black / traffic white

black / traffic white

black / traffic white

black / traffic white

Weight

26,52 kg

24,56 kg

26,52 kg

26,52 kg

26,52 kg

Weight including packaging

31,73 kg

27 kg

31,73 kg

31,73 kg

31,73 kg

Filter class

ISO Coarse 80 % (G4) / ISO ePM1 55 % (F7)

ISO Coarse 80 % (G4) / ISO ePM1 55 % (F7)

ISO Coarse 80 % (G4) / ISO ePM1 55 % (F7)

ISO Coarse 80 % (G4) / ISO ePM1 55 % (F7)

ISO Coarse 80 % (G4) / ISO ePM1 55 % (F7)

Connection diameter

125 mm / 160 mm

125 mm / 160 mm

125 mm / 160 mm

125 mm / 160 mm

125 mm / 160 mm

Connection diameter of condensation drain

not required

not required

not required

not required

not required

Width

1.260 mm

582 mm

582 mm

582 mm

582 mm

Height

230 mm

230 mm

230 mm

230 mm

230 mm

Depth

582 mm

1.260 mm

1.260 mm

1.260 mm

1.260 mm

Width with packaging

1.385 mm

710 mm

710 mm

710 mm

710 mm

Height with packaging

280 mm

245 mm

245 mm

245 mm

245 mm

Depth with packaging

730 mm

1.365 mm

1.365 mm

1.365 mm

1.365 mm

Airstream temperature at IMax

-20 °C up to 50 °C

-20 °C up to 50 °C

-20 °C up to 50 °C

-20 °C up to 50 °C

-20 °C up to 50 °C

Degree of heat provision

84 %

84 %

84 %

84 %

84 %

Max. degree of heat provision in accordance with DIN EN 13141-7 (A7)

76 %

76 %

76 %

76 %

76 %

Heat exchanger construction type

Enthalpy cross-counterflow

Enthalpy cross-counterflow

Enthalpy cross-counterflow

Enthalpy cross-counterflow

Enthalpy cross-counterflow

Humidity recovery with enthalpy heat exchanger in accordance with DIN EN 13141-7 (A2)

53 %

53 %

53 %

53 %

53 %

Position – exhaust air

left/right

left/right

left/right

left/right

left/right

Bypass

No

yes

No

yes

yes

Frost protection

No

No

integrated

integrated

integrated

Zone shutter

No

No

No

No

yes

Enthalpy heat exchanger

yes

yes

yes

yes

yes

Antifreeze circuit

yes

yes

yes

yes

yes

Summer circuit

ECO exhaust air / ECO supply air

ECO exhaust air / ECO supply air

ECO exhaust air / ECO supply air

ECO exhaust air / ECO supply air

ECO exhaust air / ECO supply air

Filter monitoring

time-controlled (controlled by differential pressure as option)

time-controlled (controlled by differential pressure as option)

time-controlled (controlled by differential pressure as option)

time-controlled (controlled by differential pressure as option)

time-controlled (controlled by differential pressure as option)

Humidity control

integrated

integrated

integrated

integrated

integrated

CO2 regulation

SKD

SKD

SKD

SKD

SKD

Air quality control (optional)

EAQ 10/3

EAQ 10/3

EAQ 10/3

EAQ 10/3

EAQ 10/3

KNX connection (optional)

K-SM

K-SM

K-SM

K-SM

K-SM

MODBUS interface

integrated

integrated

integrated

integrated

integrated

Control unit included in scope of delivery.

RLS 1 WR, App

RLS 1 WR, App

RLS 1 WR, App

RLS 1 WR, App

RLS 1 WR, App

Control unit (optional)

RLS T2 WS, RLS G1 WS

RLS T2 WS, RLS G1 WS

RLS T2 WS, RLS G1 WS

RLS T2 WS, RLS G1 WS

RLS T2 WS, RLS G1 WS

EnOcean wireless integration (optional)

E-SM

E-SM

E-SM

E-SM

E-SM

Mobile control

yes

yes

yes

yes

yes

Housing emission sound pressure level

37 dB(A) / Spacing 1m, sound absorption 10 m²

37 dB(A) / Spacing 1m, sound absorption 10 m²

37 dB(A) / Spacing 1m, sound absorption 10 m²

37 dB(A) / Spacing 1m, sound absorption 10 m²

37 dB(A) / Spacing 1m, sound absorption 10 m²

Approval number

Z-51.4-376

Z-51.4-376

Z-51.4-376

Z-51.4-376

Z-51.4-376

Packing unit

1 piece

1 piece

1 piece

1 piece

1 piece

Range

K

K

K

K

K

GTIN (EAN)

4012799950905

4012799950929

4012799950912

4012799950936

4012799950943

Power of preheating register

not specified

not specified

0,7 kW

0,7 kW

0,7 kW

* Blue markings show the differences between the products.

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings