Sound-insulated ventilation box

ESR 16 EC

Discontinued product
Article number: 0080.0085
Manufacturer: MAICO
Sound-insulated ventilation box with EC motor and swivelling fan, DN 160, alternating current
Application examples: Commercial premises, Showroom, Office, Foreman's office, Changing room
ESR 16 EC IM0009647.PNG Sound-insulated ventilation box with EC motor and swivelling fan, DN 160, alternating current
ESR 16 EC IM0013704.PNG Sound-insulated ventilation box with EC motor and swivelling fan, DN 160, alternating current

Characteristic curve

ESR 16 EC - Characteristic curve

  • ESR 16 EC IM0013665.PNG Sound-insulated ventilation box with EC motor and swivelling fan, DN 160, alternating current

Auxiliary characteristics curves for control voltage 2 - 10 V

Dimensioned drawing

ESR 16 EC - Dimensioned drawing [mm]

  • ESR 16 EC IM0015626.PNG Sound-insulated ventilation box with EC motor and swivelling fan, DN 160, alternating current

Technical data

ESR 16 EC - Technical data

Article ESR 16 EC
Air flow volume 590 m³/h
Rotating speed 3.466 1/min
Speed controllable
Rated voltage 230 V
Frequency 50 Hz
Nominal output 105 W
Power consumption 105 W
Inom 0,8 A
Imax 0,9 A
Degree of protection IP X4
Insulation class F
Installation position vertical / horizontal
Housing material Sheet steel, galvanised
Weight 12 kg
Swivelling fan
Nominal size 160 mm
Width 380 mm
Height 232 mm
Depth 447 mm
Airstream temperature at nominal current -20 °C up to 60 °C
Ambient temperature -20 °C up to 60 °C
Packing unit 1 piece
Range E
GTIN (EAN) 4012799800859
Article number 0080.0085

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA2, S1 (dB(A))

38

48

48

53

48

46

46

39

57

LWA2, S2 (dB(A))

38

49

48

54

48

45

44

38

57

LWA2, S3 (dB(A))

39

49

48

53

47

43

42

36

57

LWA2, S4 (dB(A))

40

48

50

58

48

37

36

30

59

LWA2, S5 (dB(A))

42

51

53

60

51

48

38

33

62

LWA5, S1 (dB(A))

41

50

54

55

50

51

50

43

60

LWA5, S2 (dB(A))

41

50

54

57

50

51

50

43

61

LWA5, S3 (dB(A))

40

49

54

59

49

50

48

42

62

LWA5, S4 (dB(A))

44

51

57

62

51

51

48

42

64

LWA5, S5 (dB(A))

46

53

59

64

52

52

50

45

66

LWA6, S1 (dB(A))

35

56

63

71

70

66

61

55

75

LWA6, S2 (dB(A))

36

56

64

71

70

66

61

55

75

LWA6, S3 (dB(A))

36

55

63

72

70

66

61

54

75

LWA6, S4 (dB(A))

39

58

66

77

73

69

63

57

79

LWA6, S5 (dB(A))

42

61

68

78

75

72

66

61

81

LWA2= housing sound power level in dB.

LWA5= free inlet sound power level in dB.

LWA6= free outlet sound power level in dB.

Accessories

ESR 16 EC - Accessories

Specific accessories

Product typeNameArt. No.Price*(EUR)Action
Sound insulation setKSD-D0092.0521 on request
  • On the notes

General accessories

Product typeNameArt. No.Price*(EUR)Action
Disk valve, synthetic materialTK---
Disk valve, metalTM---
Disk valve, stainless steelTM-V2A---
Disk valve, fire protectionTB, WBV---
Disk valve, metalTFA---
Disk valve, metalTFZ---
Mounting frame for TFA/TFZEBR-D---
Automatic backflow preventerAVM 160093.0008 on request
  • On the notes
Protective grilleSGR 160150.0125 on request
  • On the notes
Supply air valveZWVQ 100152.0064 on request
  • On the notes
Supply air valveZWVQ 120152.0065 on request
  • On the notes
Tubular sound absorberRSR 160092.0314 on request
  • On the notes
Tubular sound absorberRSR 16/500092.0324 on request
  • On the notes
Electrical air heaterERH 16-20082.0102 on request
  • On the notes
Electrical air heaterDRH 16-50082.0105 on request
  • On the notes
Electrical air heater with controllerERH 16-2 R0082.0142 on request
  • On the notes
Electrical air heater with controllerDRH 16-5 R0082.0143 on request
  • On the notes
Water air heaterWRH 16-20082.0118 on request
  • On the notes
Air filterTFE 16-40149.0077 on request
  • On the notes
Air filterTFE 16-50149.0061 on request
  • On the notes
Air filterTFE 16-70149.0052 on request
  • On the notes
ContactorUS 16 T0157.0769 on request
  • On the notes
PotentiometerST EC 0100157.0110 on request
  • On the notes
PotentiometerST EC 2300157.0109 on request
  • On the notes
PotentiometerST EC 30157.0111 on request
  • On the notes
Pressure and temperature control systemEAT EC0157.0119 on request
  • On the notes
Temperature control systemETL 16 PNo longer available for delivery0157.0824 on request
  • On the notes
Temperature control systemDTL 16 P0157.0825 on request
  • On the notes
Channel sensorFL 30 P0157.0780 on request
  • On the notes
Room sensorFR 30 P0157.0781 on request
  • On the notes
Air flow monitorLW 90157.0779 on request
  • On the notes
Humidity and temperature sensorFFT 30 K0157.0121 on request
  • On the notes
Temperature control systemEAT ECNo longer available for delivery0157.0113 on request
  • On the notes

Product description

Productdescription

ESR 16 EC

short description

Sound-insulated ventilation box with EC motor and swivelling fan, DN 160, alternating current

Product description

Features

  • Low energy consumption thanks to EC technology.
  • Low power consumption especially in control range.
  • Quick economical installation with standard fixing bracket.
  • Removable housing cover with clip-locks.
  • Inlet and outlet side connection couplings for direct installation in ventilation ducts.
  • With 50 mm sound absorbing rock wool, laminated with silk glass, to meet the increased requirements of especially low noise levels.
  • Centrifugal impeller with backwards curved blades.
  • Simple cleaning thanks to hinged cover.

Air flow direction

  • The airsteam direction is indicated by an arrow marked on the housing.

Motor

  • DC motor.
  • Robust motor with ball bearings, maintenance-free.
  • Temperature class B.
  • IP X4 degree of protection with closed housing cover.

Mounting instructions

  • Can be fitted in any position.

Electrical connection

  • Terminal box at front.

Safety instructions

  • The fan may be operated only if the protection against accidental contact with the impeller is guaranteed to be in accordance with DIN EN ISO 13857 for fans with free inlet or outlet. To do this, fit a protective grille.

Table of contents

Wiring diagram

ESR 16 EC - Wiring diagram

ESR EC sound-insulated ventilation box with potentiometer ST EC 010

Fuse and main switch provided by customer



ESR EC sound-insulated ventilation box with potentiometer ST EC 3

Level 1 - 3-7 V DC

Level 2 - 5-9 V DC

Level 3 - 10 V DC



Predecessor - successor

ESR 16 EC - Predecessor

Product typeNameArt. No.Action
Sound-insulated ventilation boxESR 16-2 EC0080.0711
  • On the notes
Sound-insulated ventilation boxESR 16-2 SNo longer available for delivery0080.0618
  • On the notes

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

Search

Here you can search for products, documents, contents pages etc.

Our website uses cookies in order to provide you an optimal service. Agreed

Acknowledgements Data protection