Electrical air heater with controller

DRH 40-12 R

Article number: 0082.0148
Manufacturer: MAICO
Electric air heater with integrated temperature controller, DN 400, three-phase AC
DRH 40-12 R IM0009879.PNG Electric air heater with integrated temperature controller, DN 400, three-phase AC

Characteristic curve

DRH 40-12 R - Characteristic curve Pressure losses

  1. ERH 16-2 R
  2. DRH 16-5 R
  3. DRH 20-6 R
  4. DRH 25-9 R
  5. DRH 31-12 R
  6. DRH 35-12 R
  7. DRH 40-12 R

DRH 40-12 R - Characteristic curve Increase in temperature

  1. DRH 25-9 R
  2. DRH 31-12 R
  3. DRH 35-12 R
  4. DRH 40-12 R

DRH 40-12 R - Characteristic curve Increase in temperature

  1. ERH 16-2 R
  2. DRH 16-5 R
  3. DRH 20-6 R

Dimensioned drawing

DRH 40-12 R - Dimensioned drawing [mm]

DRH 35-12 R: No rubber seal on the connection couplings

A: 400 mm

Technical data

DRH 40-12 R - Technical data

Article DRH 40-12 R
Minimum air flow volume 680 m³/h
Type of voltage Three-phase AC
Rated voltage 400 V
Frequency 50 Hz
Imax 17,3 A
Degree of protection IP 43
Installation Inside
Installation position horizontal / vertical
Housing material Sheet steel, galvanised
Weight 9,2 kg
Nominal size 400 mm
Width 400 mm
Height 481 mm
Depth 375 mm
Air heater type electrical
Heater power rating 12.000 W
Packing unit 1 piece
Range C
GTIN (EAN) 4012799821489
Article number 0082.0148

Accessories / Accessories of

DRH 40-12 R - Accessories / Accessories of

Specific accessories

Product type Name Art. No. Price*(EUR) Action
Air filter TFE 40-4 0149.0082 on request
  • On the notes
Air filter TFE 40-5 0149.0066 on request
  • On the notes
Air filter TFE 40-7 0149.0057 on request
  • On the notes
Air flow monitor LW 9 0157.0779 on request
  • On the notes

General accessories

Product type Name Art. No. Price*(EUR) Action
Contactor US 16 T 0157.0769 on request
  • On the notes

is a special accessory of

Product type Name Art. No. Price*(EUR) Action
Sound-insulated ventilation box DSR 40 S No longer available for delivery 0080.0233 on request
  • On the notes

is a general accessory of

Product type Name Art. No. Price*(EUR) Action
Quickbox ESQ 40/4 Discontinued product 0080.0030 on request
  • On the notes
Sound-insulated ventilation box ESR 40/1 No longer available for delivery 0080.0287 on request
  • On the notes
Sound-insulated ventilation box ESR 40-2 No longer available for delivery 0080.0616 on request
  • On the notes
Sound-insulated ventilation box DSR 40-2 S No longer available for delivery 0080.0623 on request
  • On the notes
Quickbox DSQ 40/4 No longer available for delivery 0080.0035 on request
  • On the notes

Product description

Productdescription

DRH 40-12 R

short description

Electric air heater with integrated temperature controller, DN 400, three-phase AC

Product description

  • Electrical air heater for ventilation systems.
  • With integrated temperature controller.
  • With non-glowing stainless steel tubular radiators.
  • FR 30 P room sensor and FL 30 P channel sensor included in the scope of delivery.
  • Increased danger of fire if tubular radiators are dirty. Install TFE air filter as a prevention.
  • Recommended accessories: LW 9 air flow monitor and TFE... air filter .

Installation instructions

  • Mount the water-air heater on the fan's pressure side in order to prevent fan motor overheating. An arrow marked on the housing shows the default air direction through the electrical air heater.
  • Mount a 1 m to 1.5 m long air duct fitting between fan and electrical air heater to ensure optimum inflow to the electrical air heater.
  • Inflow speed can be controlled using an LW 9 air flow monitor.
  • If the inflow speed falls below 1.5 m/s, the electrical air heater must be switched off.

Safety instructions

  • Increased danger of fire if the tubular radiators are dirty. Install TFE air filter as a prevention.
  • Design in accordance with VDE, Device and Product Security Laws and the corresponding EU Directives.
  • With 2 temperature limiters switching independently of each other.
  • Minimum distance to inflammable material: 150 mm (if distance is less, install appropriate insulation).

Table of contents

Wiring diagram

DRH 40-12 R - Wiring diagram

Duct fan with DRH 25-9R, DRH 31-12R, DRH 35-12R and DRH 40-12R electric air heaters

S1 - system on

S - sensor

US16 - all-pole isolating switch (contactor)

ERR... centrifugal duct fan

DRH...R electric air heater: DRH 25-9R, DRH 31-12R, DRH 35-12R, DRH 40-12R

B=Int/ext bridge must be closed

C=Do not change potentiometer setting

D=Setpoint potentiometer for MIN limitation

E=Setpoint potentiometer for MAX limitation

F=Bridge for MAX limitation, bridge must be closed!

G=If bridge is closed, MIN limitation is also active

FR30P - ext. setpoint controller (0-30°C) with room sensor

FL60P - ext. channel sensor for MIN, MAX limitation

LW9 - air flow monitor (in position N)

Installation of LW9 sensor on incoming side of air heater

0-30°C setpoint setting and recording of room temperature with FR30P

0-60°C min/max limitation in supply air channel with FL60P



Predecessor - successor

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

Search

Here you can search for products, documents, contents pages etc.

Our website uses cookies in order to provide you an optimal service. OK

Acknowledgements Data protection