Centralised ventilation unit

WR 600

No longer available for delivery
Article number: 0095.0080
Manufacturer: MAICO
Centralised ventilation unit with very effective heat recovery through cross-counter-flow exchanger, EC motors... more information
Application examples: Low-energy house, Passive energy house, Doctor's practice, Waiting room, Living room
Product data sheet
WR 600 IM0014363.PNG Centralised ventilation unit with very effective heat recovery through cross-counter-flow exchanger, EC motors with constant volumetric flow regulation, interval mode, 150 - 620 m³/h, 4 x DN 250, including RLS 1 WR control unit, DIBT and passive energy house approval, KNX connection possible
WR 600 IM0007254.PNG Centralised ventilation unit with very effective heat recovery through cross-counter-flow exchanger, EC motors with constant volumetric flow regulation, interval mode, 150 - 620 m³/h, 4 x DN 250, including RLS 1 WR control unit, DIBT and passive energy house approval, KNX connection possible

Characteristic curve

WR 600 - Characteristic curve

I - Interval operation

  1. Reduced ventilation
  2. Nominal ventilation
  3. Intensive / Party operation
  4. Recommended setting range

WR 600 - Characteristic curve Ventilation for humidity protection

Interval switch for step 1

17 min to switch on

13 min to switch off

WR 600 - Characteristic curve Ventilation for humidity protection

Interval switch for step 1

17 min to switch on

13 min to switch off

Dimensioned drawing

WR 600 - Dimensioned drawing [mm]

  1. DN 250 outgoing air
  2. DN 250 supply air
  3. DN 250 exhaust air
  4. DN 250 outside air
  5. Electrical connection
  6. Condensation drain (3/4" hose connection)

Technical data

WR 600 - Technical data

Article WR 600
Number of ventilation levels 4
Air flow volume 150 m³/h - 620 m³/h
Volumetric flow constant yes
Speed controllable
SEC average -30,9 kWh/(m²*a)
Energy efficiency class B
Type of voltage Alternating current
Rated voltage 230 V
Frequency 50 Hz/60 Hz
SPI value in accordance with DIN EN 13141-7 (A7) 0,31 Wh/m³
Power consumption 56 W - 303 W / At 100 Pa counter pressure
Imax 3 A
Degree of protection IP 00
DIBT approval yes
PHI certification No
Installation site Cellar / Storage tank / Jamb wall / Utility room / Heating room / Loft
Installation position horizontal
System type Centralised
Housing material Sheet steel, powder coated
Heat exchanger material Aluminium
Inner coating material Synthetic material
Colour pearl light grey
Weight 89 kg
Weight including packaging 106,5 kg
Filter class G4 / F7
Connection diameter 250 mm
Connection diameter of condensation drain 3/4" hose connection
Width 1.115 mm
Height 1.200 mm
Depth 505 mm
Width with packaging 1.160 mm
Height with packaging 1.390 mm
Depth with packaging 590 mm
Airstream temperature at IMax 50 °C
Max. degree of heat provision in accordance with DIN EN 13141-7 (A7) 89 %
Heat exchanger construction type Cross-counterflow
Bypass No
Frost protection External
Enthalpy heat exchanger No
Antifreeze circuit yes
Summer circuit Exhaust air with RLS D1 WR
Filter monitoring with time control
Humidity control optional with HY 5, HY 5 I, HY 10 AP, HY 10 UP
CO2 regulation SKD
Air quality control (optional) EAQ 10/2
KNX connection (optional) to be supplied by the customer
MODBUS interface No
Control unit included in scope of delivery. RLS 1 WR
Control unit (optional) RLS D1 WR
Wireless switch on/off (optional) XE 1, XS 1
EnOcean wireless integration (optional) No
Mobile control No
Housing emission sound pressure level 43 dB(A) / 46 dB(A) / 50 dB(A) / Spacing 1m, sound absorption 10 m²
Approval number Z-51.3-234
Packing unit 1 piece
Range K
GTIN (EAN) 4012799950806
Article number 0095.0080

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA2, Step 1 (dB(A))

31

37

37

39

38

35

27

17

45

LWA5, Step 1 (dB(A))

37

40

39

39

38

32

21

12

46

LWA6, Step 1 (dB(A))

38

39

40

40

43

37

23

19

48

LWA2, Level 2 (dB(A))

33

41

40

42

41

37

31

19

48

LWA5, Level 2 (dB(A))

38

43

44

42

42

35

25

16

49

LWA6, Level 2 (dB(A))

38

42

43

42

46

40

26

20

51

LWA2, Level 3 (dB(A))

34

44

44

46

45

41

35

24

52

LWA5, Level 3 (dB(A))

38

45

45

43

45

39

29

21

51

LWA6, Level 3 (dB(A))

40

46

47

46

51

45

30

22

55

LWA2= housing sound power level in dB.

LWA5= free inlet sound power level in dB.

LWA6= free outlet sound power level in dB.

LWA5, LWA6 = sound power level emitted to the free surroundings. Measured at a subsequent operating point on the connections facing the room. LWA5 Exhaust air connections, LWA6 Supply air connections.

Operating point, level 1: Air volume 230 m³/h and external pressure 100 Pa

Operating point, level 2: Air volume 345 m³/h and external pressure 100 Pa

Operating point, level 3: Air volume 460 m³/h and external pressure 100 Pa

Accessories / Spare parts

WR 600 - Accessories / Spare parts

Specific accessories

Product type Name Art. No. Price*(EUR) Action
Summer cassette WRSK 600 Discontinued product 0095.0153 on request
  • On the notes
Air filter, replacement WSF 600 0093.0689 on request
  • On the notes
Air filter, replacement WSG 600-1 0093.0688 on request
  • On the notes
Room air control RLS 1 WR 0157.0809 on request
  • On the notes
Room air control RLS D1 WR Discontinued product 0157.0828 on request
  • On the notes

General accessories

Product type Name Art. No. Price*(EUR) Action
Shutter AS 25 0151.0331 on request
  • On the notes
External grille MLZ 25 0151.0102 on request
  • On the notes
Disk valve, stainless steel TM-V2A 10 0151.0374 on request
  • On the notes
Disk valve, stainless steel TM-V2A 12 0151.0375 on request
  • On the notes
Disk valve, metal TFA 10 0151.0369 on request
  • On the notes
Disk valve, metal TFA 12 0151.0370 on request
  • On the notes
Disk valve, metal TFZ 10 0151.0364 on request
  • On the notes
Disk valve, metal TFZ 12 0151.0365 on request
  • On the notes
Mounting frame for TFA/TFZ EBR-D 10 0092.0493 on request
  • On the notes
Mounting frame for TFA/TFZ EBR-D 12 0092.0494 on request
  • On the notes
Supply air valve ZWVQ 10 0152.0064 on request
  • On the notes
Supply air valve ZWVQ 12 0152.0065 on request
  • On the notes
Tubular sound absorber RSR 10 Remaining parts 0092.0311 on request
  • On the notes
Tubular sound absorber RSR 12 Remaining parts 0092.0312 on request
  • On the notes
Tubular sound absorber RSR 25/50 Remaining parts 0092.0327 on request
  • On the notes
Tubular sound absorber RSR 8-1 0092.0591 on request
  • On the notes
Tubular sound absorber RSR 10-1 0092.0592 on request
  • On the notes
Tubular sound absorber RSR 12-1 0092.0593 on request
  • On the notes
Tubular sound absorber RSR 25/50-1 0092.0605 on request
  • On the notes
Slide-in sound absorber SDE 8 0044.0213 on request
  • On the notes
Slide-in sound absorber SDE 10 0044.0214 on request
  • On the notes
Slide-in sound absorber SDE 12 0044.0215 on request
  • On the notes
Slide-in sound absorber SDE 16 0044.0216 on request
  • On the notes
Electrical air heater DRH 25-6 0082.0107 on request
  • On the notes
Water air heater WRH 25-4 0082.0120 on request
  • On the notes
Air filter TFE 25-4 0149.0079 on request
  • On the notes
Air filter TFE 25-7 0149.0054 on request
  • On the notes
Contactor US 16 T 0157.0769 on request
  • On the notes
Thermostat TH 10 0157.0764 on request
  • On the notes
Channel sensor FL 30 P 0157.0780 on request
  • On the notes
Room sensor FR 30 P 0157.0781 on request
  • On the notes
Air flow monitor LW 9 0157.0779 on request
  • On the notes
Hygrostat HY 230 0157.0126 on request
  • On the notes
Hygrostat HY 230 I 0157.0127 on request
  • On the notes
CO2 sensor SKD 0157.0345 on request
  • On the notes
Tubular sound absorber RSR 8 No longer available for delivery 0092.0310 on request
  • On the notes
Air filter TFE 25-5 No longer available for delivery 0149.0063 on request
  • On the notes
Radio switch XS 1 No longer available for delivery 0157.0344 on request
  • On the notes
Radio receiver XE 1 No longer available for delivery 0157.0343 on request
  • On the notes
Temperature control system ETL 16 P No longer available for delivery 0157.0824 on request
  • On the notes
Air quality controller EAQ 10/2 No longer available for delivery 0157.0834 on request
  • On the notes
Hygrostat HY 10 AP No longer available for delivery 0157.0358 on request
  • On the notes
Hygrostat HY 10 UP No longer available for delivery 0157.0357 on request
  • On the notes

Spare parts

Product description

Productdescription

WR 600

short description

Centralised ventilation unit with very effective heat recovery through cross-counter-flow exchanger, EC motors with constant volumetric flow regulation, interval mode, 150 - 620 m³/h, 4 x DN 250, including RLS 1 WR control unit, DIBT and passive energy house approval, KNX connection possible

Product description

Features

  • Special energy savings due to DC motors with EC technology.
  • With automatic volumetric flow regulation for constant air quantities.
  • Sheet steel, powder coated housing.
  • Colour pearl light grey.
  • Inner coating of heat resistant plastic material (EPP), non-hygroscopic.
  • Simple filter change is possible without tools.
  • 2 x G4 filter, 1 x F7 filter.
  • 2 DN 250 duct connections with double lip seals each. For directly connecting up tubular sound absorbers.
  • DIBT approval and PH certification.
  • Connection to KNX systems possible.

Control unit

  • RLS 1 WR control unit is included in the scope of delivery as standard.
  • Filter change warning displayed on the control unit.
  • Set the 4 ventilation levels using buttons.
  • Fault display.
  • Other control units can be connected in parallel.

Heat exchanger

  • Cross-counterflow plate heat exchanger made of aluminium.
  • The heat exchanger can be removed easily once the front plate has been unscrewed.
  • The heat exchanger can be easily cleaned using water.

Frost protection

  • Guaranteed frost protection ensures that the heat exchanger does not freeze.
  • The frost protection feature switches the supply air fan off when the outgoing air temperature is too low and automatically back on again.
  • Recommendation: Combine units with heat recovery with a brine earth heat exchanger.

Energy-efficient fans

  • 2 centrifugal DC fans, curved to the front. In the supply or exhaust air.
  • 4 ventilation levels:
    • I = Interval / vacation operation for humidity protection
    • 1 = Reduced ventilation
    • 2 = Nominal ventilation
    • 3 = Intensive / party operation
  • The air volume is linearly adjustable.

Mounting instructions

  • Feet for installation.
  • Ensure access to condensation connection on side.
  • Housing covers can be unscrewed.
  • Provide sound absorbers on the inlet and outlet sides.

Electrical connection

  • Ready for service.
  • Prepared for connection of sensors.
  • Potential-free contact e.g. for operating display.
  • Central inclusion in KNX/EIB bus possible.

Condensation drain

  • Condensation is drained out from the side of the unit. Condensation drain (3/4" hose connection) to connect up to a siphon.
  • Stable foamed-in condensation tank.

Plus function (summer operation)

  • In eco mode, only the exhaust fan runs, so around 50 % less power is used. Possible with RLS D1 WR digital control.

Table of contents

Wiring diagram

WR 600 - Wiring diagram

Wiring diagram for WR 600 ventilation with RLS D1 WR room air control (plus function)

A - WR 600 / RB 600 ventilation unit

A1 - WR 600 / RB 600 terminal box

A2 - Control circuit board

B1 - RLS 1 WR or RB-ZF4 room air control

W1 -230 VAC connecting cable

W2' - Shielded control cable (to be supplied by customer) for RLS D1 WR / RB-D1-ZF4 room air control. Room air control B (RLS D1 WR / RB-D1-ZF4) can also be connected instead of room air control B1 (RLS 1 WR / RB-ZF4). External diameter of the shielded cable 3.2...6.5 mm, e.g. LIYCY 2 x 0.75 mm².

W2 - Control cable (to be supplied by customer) for RLS 1 WR / RB-ZF4 room air control. External diameter of the control cable 3.2...6.5 mm, e.g. LIYY 6 x 0.34 mm²

F - Mains filter

MP1 - Motor board 1 for supply air fan

MP2 - Motor board 2 for exhaust air fan

M1 - Supply air fan

M2 - Exhaust air fan

S - Door contact switch/activated via front plate

T-min - Frost protection temperature sensor

S1 [blue] - setting potentiometer for supply air volumetric flow, ventilation level 1

S2 [blue] - setting potentiometer for supply air volumetric flow, ventilation level 2

S3 [blue] - setting potentiometer for supply air volumetric flow, ventilation level 3

S1 [red] - setting potentiometer for exhaust air volumetric flow, ventilation level 1

S2 [red] - setting potentiometer for exhaust air volumetric flow, ventilation level 2

S3 [red] - setting potentiometer for exhaust air volumetric flow, ventilation level 3

Jumper settings

J 1-3 - Unit type, 011 = WR 600 / RB 600

J 4-5 - Frost protection temperature

J 6 - No function

J 7 - Time limitation (60 minutes) LS3 is activated

J 8 - RLS 1 WR/RB-ZF4 or RLS D1 WR/RB-D1-ZF4 room air control is selected

J 9 - Humidity protection is blocked at switch position OFF. Room air control: switch setting OFF (standby) is released

J 10 - 0 - 10 V input for CO2 sensor blocked

Further connection options

W3 - Connecting cable (provided by customer) for external operating display.

k1- Potential-free relay contact k1 (max. 3 A / 250 VAC, 2 A / 30 VDC). Contact k1 is closed when the ventilation unit is running.

W3' - Connecting cable (to be supplied by customer) for external CO2/VOC sensor or external hygrostat. Hygrostat with potential-free contact.

W3" -Connecting cable (provided by customer) for external differential pressure controller. Differential pressure controller with potential-free relay contact. Minimum switching capacity of relay contact: 230 VAC / 2A. Remove J1 bridge on A2 control circuit board.



WR 600 ventilation unit with RLS 1 WR room air control and CO<sub>2</sub>sensor

Connection of a CO2 sensor for the demand-driven supply of fresh air. The ventilation unit only reacts to the CO2sensor if ventilation level 2 (nominal ventilation) is selected at the room air control.

A1 - electrical terminal box WR 600

A2 - control circuit board: Jumper 10 (CO2) set

B1 - room air control RLS 1 WR

CO2 - CO2sensor SKD

W1 - 230 V AC connecting cable

W2 control cable for room air control

W3' - connecting cable for external CO2sensor (to be supplied by the customer). Connection to control circuit board A2 at terminals “CO2” and “OT”. Set jumper 10 (CO2) to release the feature, see figure.

Switching points for CO2sensor

< 900 ppm, ventilation unit switches to ventilation level 1. Ventilation level 2 is shown at the room air control.

> 1,000 ppm, ventilation unit switches from ventilation level 1 to ventilation level 2.

> 1,100 ppm, ventilation unit switches to ventilation level 3. Ventilation level 2 is shown at the room air control.

< 1,000 ppm, ventilation unit switches from ventilation level 3 to ventilation level 2.



WR 600 ventilation unit with RLS 1 WR room air control and differential pressure controller

Parallel operation of fireplace and ventilation unit

The differential pressure controller P is a safety device, which allows a ventilation system to be operated at the same time as an air-ventilated fireplace.

The differential pressure controller, e.g. Wodtke DS 01, prevents a ventilation unit that is connected to this safety device being operated, if there is negative pressure in the living room.

The potential-free relay contact (n/c) in the differential pressure controller switches the fans in the ventilation unit off, if required. Relay contact k is connected in series to the fans' supply voltage for this purpose.

This blocks the room air control RLS 1 WR. The LED display goes out. The unit is only released again when the differential pressure controller switches the fans back on. The ventilation unit runs at the same ventilation level as before it was blocked.

When selecting the differential pressure controller, note the technical data of the switching output (potential-free relay contact k). Minimum switching capacity: 230 V AC, 2A

The connection between the differential pressure controller and ventilation unit is made with W3" connecting cable.

The potential-free relay contact k of the differential pressure controller P is connected to control circuit board A2 at terminals "N" and " ".

Before this, the jumpers on the terminals "N" and " " on the control circuit board A2 must be removed.

A1 - electrical terminal box WR 600

A2 - control circuit board

B1 - room air control RLS 1 WR

P - differential pressure controller with potential-free relay contact k (provided by customer)

k - switching output, potential-free relay contact

W3" - connecting cable for differential pressure controller (provided by customer)

ABL - exhaust air

ZUL - supply air



WR 600 ventilation unit with up to 5 RLS 1 WR room air controls

Up to 5 RLS 1 WR room air controls can be connected to the ventilation unit. No CO2 sensor should be connected if several room air controls are connected.

A1 - electrical terminal box WR 600

A2 - control circuit board: Jumper setting = Factory setting

B1 - 1 RLS 1 WR room air control

B2 - 2. RLS 1 WR room air control

W1 - 230 V AC connecting cable

W2 - control cable for room air control

V - distributor (supplied by the customer)

The ventilation unit is factory-set for the connection of the RLS 1 WR room air control. Jumper 8 is set on the control circuit board A2.



WR 600 ventilation unit with RSL 2 F room air control and HY 5 hygrostat

Connection of a hygrostat for demand-driven humidity extraction. This must have a potential-free switching output, e.g. Maico Hygrostat HY 5.

The hygrostat always switches the ventilation unit to ventilation level 3 if the defined humidity value is exceeded. If the humidity in the room drops, the ventilation unit switches back to the previously selected ventilation level.

If you switch manually or using the timer from ventilation level 3 to level 2 or 1, this deactivates the automatic function of the hygrostat temporarily. This is then switched back to active if the level drops below the hygrostat set point once.

A1 - electrical terminal box WR 600

A2 - control circuit board: Jumper 10 (CO2) not set / Jumper 8 not set

B1 - room air control RLS 2 F

r.F. (relative humidity) r.F. (relative humidity) - Hygrostat HY 5, see accessories

W1 - 230 V AC connecting cable

W2 - control cable for room air control

W3' - connecting cable for an external hygrostat (to be supplied by the customer). Connection to control circuit board A2 at “CO2” terminal, see figure.

Set the switching point at the hygrostat manually.

Never connect a hygrostat and a CO2 sensor at the same time.



Wiring diagram for WR 600 ventilation with RLS 1 WR room air control

A - WR 600 ventilation unit

A1 - electrical terminal box

A2 - control circuit board

B/B1 - room air control

W1 - 230 V AC connecting cable

W2 - control cable for room air control

F - mains filter

MP1 - motor board 1 for supply air fan

MP2 - motor board 2 for exhaust air fan

M1 - supply air fan

M2 - exhaust fan

S - door contact switch: activated by front plate

Tmin - Frost protection temperature sensor

Supply air

S1 (blue) - Potentiometer adjuster, ventilation level 1

S2 (blue) - Potentiometer adjuster, ventilation level 2

S3 (blue) - Potentiometer adjuster, ventilation level 3

Exhaust air

S1 (red) - Potentiometer adjuster, ventilation level 1

S2 (red) - Potentiometer adjuster, ventilation level 2

S3 (red) - Potentiometer adjuster, ventilation level 3

Jumper settings

J 1-3 Potentiometer volumetric flow range

J 4-5 Frost protection temperature

J 6 No function

J 7 Ventilation level 3 is reset after an hour

J 8 Room air control (RLS 1 WR factory setting)

J 9 Switching off the ventilation unit possible (on/off active)

J 10 Hygrostat connection released

Further connection options

W3/W3' - Connection cable (supplied by customer) for hygrostat, CO2 sensor, external operating display, thermostat or differential pressure controller.

k1 - Potential-free relay contact (max. 3A / 250 VAC, 2A / 30 VDC). The contact is closed when the ventilation unit is running.

ABL - exhaust air

ZUL - supply air

N - mains

BA - operating display

BT - operator unit



Wiring diagram for WR 600 ventilation with RLS 2 F room air control

A - WR 600 ventilation unit

A1 - electrical terminal box

A2 - control circuit board

B/B1 - room air control

W1 - 230 V AC connecting cable

W2 - control cable for room air control

F - mains filter

MP1 - motor board 1 for supply air fan

MP2 - motor board 2 for exhaust air fan

M1 - supply air fan

M2 - exhaust fan

S - door contact switch: activated by front plate

Tmin - Frost protection temperature sensor

Supply air

S1 (blue) - Potentiometer adjuster, ventilation level 1

S2 (blue) - Potentiometer adjuster, ventilation level 2

S3 (blue) - Potentiometer adjuster, ventilation level 3

Exhaust air

S1 (red) - Potentiometer adjuster, ventilation level 1

S2 (red) - Potentiometer adjuster, ventilation level 2

S3 (red) - Potentiometer adjuster, ventilation level 3

Jumper settings

J 1-3 Potentiometer volumetric flow range

J 4-5 Frost protection temperature

J 6 No function

J 7 Ventilation level 3 is reset after an hour

J 8 Room air control (RLS 1 WR factory setting)

J 9 Switching off the ventilation unit possible (on/off active)

J 10 Hygrostat connection released

Further connection options

W3/W3' - Connection cable (supplied by customer) for hygrostat, CO2 sensor, external operating display, thermostat or differential pressure controller.

k1 - Potential-free relay contact (max. 3A / 250 VAC, 2A / 30 VDC). The contact is closed when the ventilation unit is running.

ABL - exhaust air

ZUL - supply air

N - mains

BA - operating display

BT - operator unit



WR 600 ventilation unit with RSL 1 WR room air control and HY 5 hygrostat

Connection of a hygrostat for demand-driven humidity extraction. This must have a potential-free switching output, e.g. Maico Hygrostat HY 5.

The hygrostat always switches the ventilation unit to ventilation level 3 if the defined humidity value is exceeded. If the humidity in the room drops, the ventilation unit switches back to the previously selected ventilation level.

If you switch manually from ventilation level 3 to level 2 or 1, this deactivates the automatic function of the hygrostat temporarily. This is then switched back to active if the level drops below the hygrostat set point once.

A1 - electrical terminal box WR 600

A2 - control circuit board: Jumper 10 (CO2) open

B1 - room air control RLS 1 WR

r.F. (relative humidity) r.F. (relative humidity) - Hygrostat HY 5, see accessories

W1 - 230 V AC connecting cable

W2 - control cable for room air control

W3' - connecting cable for an external hygrostat (to be supplied by the customer). Connection to control circuit board A2 at “CO2” terminal, see figure.

Set the switching point at the hygrostat manually.

Never connect a hygrostat and a CO2 sensor at the same time.



WR 600 ventilation unit with RSL 1 WR or RLS 2 F room air control and electric air heater

If the heat recovery unit is installed in a passive-energy house, a heat register in the outside air is necessary, in order to guarantee a permanent air exchange.

It preheats cold outside air and keeps the heat exchanger free of frost. The switch-on temperature of the TH 10 should be set to -3℃.

If the outside air temperature gets too cold, the external frost protection heating of the DRH 25-6 switches on and guarantees an uninterrupted ventilation operation.

The switch-off difference should be set to 5 K. Optionally, the switch-on temperature can be adjusted manually using the setting wheel at the TH 10.

The air flow controller sensor "S1" must be installed in the direction of flow, at least 30 cm ahead of the electrical air heater. The TH 10 temperature sensor "R1" must be installed in the air flow direction, at least 50 cm after the electrical air heater.

LW 9 - air flow monitor

S1 - air flow monitor sensor before the DRH..

JP1 - plug jumper on operating mode “H”. Relay switches on as the temperature drops.

TH 10 - thermostat

R1 - temperature sensor after DRH..

US 16 T- universal contactor

DRH 25-6 - electrical air heaters

S - sensor

We recommend the filter box TFE 25-4 (with G4 filter) to protect the electrical heat register against dirt. If a filter box is used, the G4 filter in the outside air channel can be removed from the heat recovery unit.

A ground collector and brine-air heat exchanger can be used to keep the heat exchanger free of frost.

For external heat register, filter box, outside air and outgoing air channel: These must be diffusion-resistant insulated to protect against condensation.



Predecessor - successor

WR 600 - Predecessor

Product type Name Art. No. Action
Aeronom room air system WS 600 No longer available for delivery 0095.0056
  • On the notes

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings