Centralised exhaust air unit

ZEG 2000 P

No longer available for delivery
Article number: 0086.0203
Manufacturer: MAICO
High pressure centralised exhaust air unit without heat recovery
Application examples: Low-energy house, Single-family house, Apartment, Living room, Redevelopment
Product data sheet
ZEG 2000 P IM0009838.PNG High pressure centralised exhaust air unit without heat recovery

Characteristic curve

ZEG 2000 P - Characteristic curve

Dimensioned drawing

ZEG 2000 P - Dimensioned drawing [mm]

Technical data

ZEG 2000 P - Technical data

Article ZEG 2000 P
Air flow volume 310 m³/h / System pressure at 100 Pa
Rotating speed 690 1/min / 1.145 1/min / 1.825 1/min
SEC average -9,1 kWh/(m²*a)
Energy efficiency class F
Type of voltage Alternating current
Rated voltage 230 V
Power consumption 14 W / 42 W / 92 W
Imax 0,14 A / 0,3 A / 0,4 A
Degree of protection IP 20
Installation site Cellar / Storage tank / Jamb wall / Utility room / Heating room
Installation position vertical / horizontal
System type Centralised
Material Synthetic material
Weight 3,4 kg
Weight including packaging 3,84 kg
Connection diameter 125 mm
Width 360 mm
Height 280 mm
Depth 278 mm
Width with packaging 350 mm
Height with packaging 295 mm
Depth with packaging 370 mm
Sound pressure level 33 dB(A) / 41 dB(A) / 49 dB(A)
Packing unit 1 piece
Range K
GTIN (EAN) 4012799862031
Article number 0086.0203

 

63 Hz

125 Hz

250 Hz

500 Hz

1 kHz

2 kHz

4 kHz

8 kHz

Total

LWA2, high (dB(A))

23

41

54

48

49

45

45

42

57

LWA2, medium (dB(A))

21

35

43

42

42

43

33

28

49

LWA2, low (dB(A))

21

20

31

32

39

30

7

5

41

LWA5, high (dB(A))

42

55

54

54

52

49

53

48

61

LWA5, medium (dB(A))

32

43

44

44

42

37

39

31

50

LWA5, low (dB(A))

22

26

30

31

28

17

19

7

36

LWA8, high (dB(A))

41

48

55

55

62

58

55

51

65

LWA8, medium (dB(A))

31

36

43

44

50

47

41

33

53

LWA8, low (dB(A))

22

22

31

36

43

30

13

3

44

LWA2= housing sound power level in dB.

LWA5= free inlet sound power level in dB.

LWA8= housing and free outlet sound power level in dB.

Accessories

ZEG 2000 P - Accessories

Specific accessories

Product type Name Art. No. Price*(EUR) Action
Room air control RLS 3 0157.0831 on request
  • On the notes

General accessories

Product type Name Art. No. Price*(EUR) Action
MAICOTherm ventilation duct system, thermally insulated MAICOTherm MT thermally-insulated ventilation duct system - - -
Roof outlet DF - - -
Roofing tile DP - - -
Mounting clamp BS - - -
Rain protection grille RG - - -
MAICOFlex ventilation duct system, round Flexible round MAICOFlex MF ventilation duct system - - -
MAICOFlex ventilation duct system, round Flexible round MAICOFlex ventilation duct system - - -
Roofing tile DP - - -
MAICO FFS ventilation duct system, flat MAICO FFS flexible flat ventilation duct system - - -
Stainless steel cowl LH-V2A 12 0151.0378 on request
  • On the notes
Stainless steel cowl LH-V2A 15 0151.0379 on request
  • On the notes
Outgoing air wall connection KW-FL 12E 0152.0075 on request
  • On the notes
Outgoing air wall connection KW-FL 12W 0152.0076 on request
  • On the notes
Outgoing air wall connection KW-FL 16E 0152.0079 on request
  • On the notes
Outgoing air wall connection KW-FL 16W 0152.0080 on request
  • On the notes
Outside air opening ALD 10 0152.0054 on request
  • On the notes
Outside air opening ALD 125 0152.0067 on request
  • On the notes
Outside air opening ALD 125 VA 0152.0068 on request
  • On the notes
Outside air opening ALD 160 0152.0069 on request
  • On the notes
Outside air opening ALD 160 VA 0152.0070 on request
  • On the notes
Internal grille ESG 10/2 0059.0947 on request
  • On the notes
Door ventilation grille MLK 30 white 0151.0123 on request
  • On the notes
Door ventilation grille MLK 45 white 0151.0126 on request
  • On the notes
Exhaust and supply air valve AZV 100 0152.0087 on request
  • On the notes
Disk valve, synthetic material TK 10 0151.0192 on request
  • On the notes
Disk valve, synthetic material TK 12 0151.0198 on request
  • On the notes
Disk valve, metal TM 10 0151.0194 on request
  • On the notes
Disk valve, metal TM 12 0151.0196 on request
  • On the notes
Disk valve, stainless steel TM-V2A 10 0151.0374 on request
  • On the notes
Disk valve, stainless steel TM-V2A 12 0151.0375 on request
  • On the notes
Disk valve, metal TFA 10 0151.0369 on request
  • On the notes
Disk valve, metal TFA 12 0151.0370 on request
  • On the notes
Mounting frame for TFA/TFZ EBR-D 10 0092.0493 on request
  • On the notes
Mounting frame for TFA/TFZ EBR-D 12 0092.0494 on request
  • On the notes
Grease filter element for exhaust air FFE 10 0092.0506 on request
  • On the notes
Flexible aluminium duct AFR 125 0055.0091 on request
  • On the notes
Tubular sound absorber RSR 12 Remaining parts 0092.0312 on request
  • On the notes
Tubular sound absorber RSR 12/50 0092.0322 on request
  • On the notes
Slide-in sound absorber SDE 8 0044.0213 on request
  • On the notes
Slide-in sound absorber SDE 10 0044.0214 on request
  • On the notes
Slide-in sound absorber SDE 12 0044.0215 on request
  • On the notes
Stainless steel cowl LH-V2A 16 No longer available for delivery 0151.0380 on request
  • On the notes
Folded spiral-seams duct WFR 125 No longer available for delivery 0055.0077 on request
  • On the notes
Internal grille, adjustable AZE 100 No longer available for delivery 0059.0959 on request
  • On the notes
Outside air opening ALD 10 T No longer available for delivery 0152.0055 on request
  • On the notes
Outside air opening ZE 45 F white No longer available for delivery 0152.0044 on request
  • On the notes

Product description

Productdescription

ZEG 2000 P

short description

High pressure centralised exhaust air unit without heat recovery

Product description

Features

  • Central ventilation unit.
  • For simultaneous air extraction of a number of rooms in single family-unit houses or apartments.
  • High pressure through centrifugal impeller.
  • Supply air intake by means of decentralised outside air openings, e.g. ALDs.
  • 3 ventilation levels can be set.
  • Up to 3 intake sockets for exhaust air, suitable for ducts with DN 125. The intake sockets can be broken-out if need be.
  • 1 DN 125 exhaust socket for outgoing air.

Motor

  • Motor designed for continuous operation.
  • Thermal overload protection as standard feature.

Mounting instructions

  • The housing can be fastened in any position to beams, walls or ceilings.

Electrical connection

  • When delivered, the device is assembled and ready for service.

Table of contents

Wiring diagram

ZEG 2000 P - Wiring diagram

ZEG 2000 P

1 = Low power

2 = Medium power

3 = High power

V distributor (supplied by the customer)



ZEG 2000 P with RLS 3 room air control

S1 - On / Off

S2 - low, medium, high power



Predecessor - successor

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings