Room air control

RLS 45 K

Article number: 0157.0360
Manufacturer: MAICO
Room air control as an accessory for the PP 45 K, PP 45 O, PPB 30 K and PPB 30 O final assembly kit, up to six... more information

Product data sheet
RLS 45 K IM0017090.PNG Room air control as an accessory for the PP 45 K, PP 45 O, PPB 30 K and PPB 30 O final assembly kit, up to six units can be connected, 5 ventilation levels can be set, programs: continuous ventilation with heat recovery, cross-ventilation without heat recovery and sensor-controlled automatic mode, time-limited intensive ventilation, time-limited switch-off, communication with exhaust air units, ModBus, safety shutdown, configuration with PC / laptop
RLS 45 K IM0019952.PNG Room air control as an accessory for the PP 45 K, PP 45 O, PPB 30 K and PPB 30 O final assembly kit, up to six units can be connected, 5 ventilation levels can be set, programs: continuous ventilation with heat recovery, cross-ventilation without heat recovery and sensor-controlled automatic mode, time-limited intensive ventilation, time-limited switch-off, communication with exhaust air units, ModBus, safety shutdown, configuration with PC / laptop

Characteristic curve

Dimensioned drawing

Technical data

RLS 45 K - Technical data

Article RLS 45 K
Rated voltage 230 V
Mains cable 3 x 1,5 mm²
Installation site Wall
Type of installation Recessed-mounted
Material Synthetic material
Colour Pure white, similar to RAL 9010
Weight 0,11 kg
Weight including packaging 0,34 kg
Width 80 mm
Height 80 mm
Depth 49 mm
Width with packaging 81 mm
Height with packaging 81 mm
Depth with packaging 50 mm
Packing unit 1 piece
Range K
GTIN (EAN) 4012799573609
Article number 0157.0360

Accessories / Accessories of

RLS 45 K - Accessories / Accessories of

Specific accessories

is a special accessory of

Product description

Productdescription

RLS 45 K

short description

Room air control as an accessory for the PP 45 K, PP 45 O, PPB 30 K and PPB 30 O final assembly kit, up to six units can be connected, 5 ventilation levels can be set, programs: continuous ventilation with heat recovery, cross-ventilation without heat recovery and sensor-controlled automatic mode, time-limited intensive ventilation, time-limited switch-off, communication with exhaust air units, ModBus, safety shutdown, configuration with PC / laptop

Product description

Features

  • The room air control is needed as an accessory for the PP 45 K, PP 45 O or PPB 30 K, PPB 30 O final assembly kits.
  • For the PP 45 RC unit series, the RLS 45 K wired control can optionally be used instead of the DS 45 RC radio switch. A combination of RLS 45 K with the EnOcean extension module PP 45 EO is then needed.
  • An RLS 45 K room air control can be used to control up to 6 fans at the same time, e.g. 6 x PP 45 units or 4 x PP 45 units + 1 x PPB 30 or up to 3 x PPB 30 units.

Table of contents

Wiring diagram

RLS 45 K - Wiring diagram

RLS 45 K - PushPull 45 comfort room air control

PP 45 K - PushPull 45 comfort fan unit

Fan 1.1 - fan unit 1, unit pair 1

Fan 2.1 - fan unit 2, unit pair 1

Fan 1.2 - fan unit 1, unit pair 2

Fan 2.2 - fan unit 2, unit pair 2

Fan 1.3 - fan unit 1, unit pair 3

Fan 2.3 - fan unit 2, unit pair 3

S1 - Button/switch for additional function (sleep, intensive, disbalance, safety function)

UP-L -Recessed-mounted distributor connection for fan units, connection of all fan units in star shape to distributor

W-F1 - Fan 1 control cable, recommended control cable J-Y (ST) Y 2x2x0.8mm. Max. length to distributor 4m.

W-F2 - Fan 2 control cable, recommended control cable J-Y (ST) Y 2x2x0.8mm. Max. length to distributor 4m.

W1.X - Fan unit control cable, recommended control cable J-Y (ST) Y 2x2x0.8mm. Max. cable length from UP-L distributor to PP 45 ventilation unit = 25m.

W2.X - Fan unit control cable, recommended control cable J-Y (ST) Y 2x2x0.8mm. Max. cable length from UP-L distributor to PP 45 ventilation unit = 25m.

W3 - Bus (RS-485) connection cable, recommended control cable J-Y (ST) Y 2x2x0.8mm. Max. cable length to the sensors, RLS, LT and EnOcean module approx. 100m. Alternatively, this connection can also be used as a ModBus RTU interface.



RLS 45 K - PushPull 45 Comfort room air control

PP 45 K - PushPull 45 Comfort fan unit

PPB 30 K - PushPull Balanced 30 Comfort fan unit

Fan 1.1 - fan unit 1, unit pair 1

Fan 2.1 - fan unit 2, unit pair 1

Fan 1.2 - fan unit 1, unit pair 2

Fan 2.2 - fan unit 2, unit pair 2

S1 - Button/switch for additional function (sleep, intensive, disbalance, safety function)

UP-L - Recessed-mounted distributor connection, connection of all fan units in star shape to distributor

W-F1 - Fan 1 control cable, recommended control cable J-Y(ST)Y 2x2x0.8mm. Max. length to distributor 4m.

W-F2 - Fan 2 control cable, recommended control cable J-Y(ST)Y 2x2x0.8mm. Max. length to distributor 4m.

W-B1 - Bus PPB control cable, recommended control cable J-Y(ST)Y 2x2x0.8mm. Max. length to distributor 4m.

W1.X - Fan unit control cable, recommended control cable J-Y(ST)Y 2x2x0.8mm. Max. cable length from UP-L distributor to PP 45 ventilation unit = 25m.

W2.X - Fan unit control cable, recommended control cable J-Y(ST)Y 2x2x0.8mm. Max. cable length from UP-L distributor to PP 45 ventilation unit = 25m.

W-PPB - BBP 30 (bus) control cable, recommended control cable J-Y(ST)Y 2x2x0.8mm. Max. cable length from UP-L distributor to PP 45 ventilation unit = 25m.

W3 - Connecting cable switch/pushbutton for activation of special functions (exhaust air mode, intensive ventilation), recommended control cable LiYY 2*0.5 mm². Max. cable length 25 metres.



RLS 45 K - PP 45 Comfort room air control

PP 45 LT - PP 45 power unit

PP 45 EO - PP 45 EnOcean radio module

PP 45 HY - PP 45 humidity sensor for recessed mounting

PP 45 CO2 - PP 45 CO2 sensor for recessed mounting

PP 45 VOC - PP 45 VOC sensor for recessed mounting

Fan 1.1-1.3 - Fan unit 1 and 3 on RLS master

Fan 2.1-2.3 - Fan unit 2 and 4 on RLS master

W-PPB - Fan unit 5 (BBP 30 K) on RLS master connecting cable for bus (RS-485), recommended control cable J-Y(ST)Y 2x2x0.8mm². Max. cable length to the PPB 30 K, 25 metres from the star point

Fan 3 + 4 G1-3 - Fan unit 6,7,8 on RLS slave 1

Fan 5.1-5.3 - Fan unit 9,11,13 on RLS slave 2

Fan 6.1-6.3 - Fan unit 10,12,14 on RLS slave 2

S1 - Button/switch for additional function (sleep, intensive, disbalance, safety function)

UP-B - Recessed-mounted distributor bus, connection of RLS, LT, EO and sensors using RS-485 bus interface

W1.X - Bus (RS-485) connection cable, recommended control cable J-Y(ST)Y 2x2x0.8mm. Max. cable length to the sensors, RLS, LTs and EnOcean module approx. 100 m. Alternatively, this connection can also be used as a ModBus RTU interface.



RLS 45 K - 45 comfort room air control / ModBus interface also available for object variant.

X1.1 - terminal mains connection

X1.2 - connection terminal bus/fan

W1 - GLT (ModBus) connection cable, recommended control cable J-Y (ST) Y 2x2x0.8mm. Max. cable length to gateway approx. 100m. Set parameters and undertake addressing by means of service mode or IBS* (commissioning software)

*IBS only in conjunction with the RLS 45 K

Interface info:

ModBus mode: RTU

Baud rate: 9600/19200

Data bits 8

Parity: Even

Stop bits 1

Address: 10 (basic setting)



Predecessor - successor

RLS 45 K - Predecessor

Product type Name Art. No. Action
Room air control RLS PP-K 0157.0199

Notes
Inquiry
Product comparison
The wish list option allows you to make a note of all the products you are interested in. You can change your wish list as often as you want to. You can change the quantity and item position of the products, go back to the product page, download product data sheets, delete items and mark products as optional. You can save your wish list to your computer and then call it up again at a later time to make more changes, if required. Using the list, you can then download the tender text for all the products you have saved to the list, create an enquiry or compare products.
Assort Product type Name Art. No. PDF Range List price* (EUR) Quantity Optional Total gross amount (EUR)
There are no products on the list
Save wish list on local computer
Load wish list from local computer

On this website, technologies such as cookies and measurements of reach (targeting and tracking) are used (services). This means that personal information such as the IP address and browser information is processed to continuously improve our website as well as to display to you customised content that corresponds to your individual interests. You may of course influence the use of this information through the settings you choose. The settings you have chosen are stored in a necessary selection cookie. With the exception of the selection cookie mentioned above, technically non-essential cookies and measurements of reach are only used if you provide permission in advance by clicking “ACCEPT ALL AND CLOSE”. Details and options for customising your consent can be found under Data protection settings.

Here you can select a variety of different categories of services or cookies. By activating the corresponding “Statistics & analytics” checkbox and confirming “Save settings”, you can give your informed consent to the use of cookies for customisation purposes. At the bottom of the website under “Data protection settings”, you can change or revoke your consent and settings for the individual services at any time with effect for the future.

Necessary cookies are absolutely necessary for the operation of the website. Without these cookies, the website would not function properly.

These cookies and services collect and process data for statistics and analytics and thus enable further improvements of this website for users. Google Analytics and Google Adwords Conversion are used for this purpose. You will find a detailed description of such use in our Privacy Policy.

Save settings ACCEPT ALL AND CLOSE Data protection settings